The Situation

The basement of a condominium building reportedly experienced a flood, subsequently damaging the fire pump controller, automatic transfer switch (ATS), and ancillary electrical equipment.

Equipment Impacted

  • Fire Pump Controller

  • Automatic Transfer Switch (ATS)

  • Ancillary Electrical Equipment

     

     

Value-Driven Solutions

Comprehensive Equipment Condition Evaluation

Our experts analyzed corrosion patterns, inspected enclosure interiors, and performed operational testing to determine the true condition of the systems.

Defensible Cause of Loss Determination

ILC determined the corrosion was caused by long-term basement moisture exposure rather than the reported flood event. This provided the client with a technically supported and defensible cause-of-loss determination.

Technical Validation of Repair Scope

ILC inventoried the damaged machinery and equipment and performed a technical review of multiple vendor repair proposals to confirm scope accuracy, repair feasibility, and the use of Like, Kind, and Quality restoration methods.

Water Damage with Fire Pump System

The Results

Accurate and Cost-Effective ClaimResolution


ILC validated appropriate repair strategies while preventing unnecessary replacement or expanded scopes, ensuring an accurate and cost-effective claim resolution.

Vendor Proposal and Cost Analysis


ILC evaluated competitive repair options and leveraged technical expertise infire protection machinery and equipment to assess vendor pricing and repair methodology.

Verified Cost Savings WhileMaintaining System Reliability


ILC secured a competitive repair quote from a fire system vendor, reducing electrical supply repair costs by $3,635 while maintaining system functionality and compliance.

 